Регистрация
deal.by
Frequency voltage current converter KFU8-FSSP-1.D-Y322444 - фото 1 - id-p95199207
Характеристики и описание

Техническая спецификация в PDF  

Описание оборудования

Frequency voltage current converter
40 kHz version

Functional safety related parameters

MTTFd100 a

Supply

Rated voltage20 ... 30 V DC
Fusingexternal fusing 4 A
Power consumption< 5 W

Indicators/operating means

Type4-digit, 7-segment red display, 7 mm digit height
Display interval0.002 ... 9999 Hz or
0.01 ... 9999 min-1
Parameter assignmentkeypad-driven menu

Input 2

Switching pointhigh: 16 ... 30 V DC; max.10 mA; Ri ? 3 kOhm
low: 0 ... 6 V DC
Connectionterminals 7+, 13- sensor supply
terminals 14, 15 NPN/PNP input (galvanically isolated)
Connectable sensor types2-, 3-, or 4-wire proximity switches and incremental rotary encoder
Sensor supplyRated voltage - 1.5 V non-stabilised; ? 30 mA short-circuit protected

Output

Analog voltage output0 ... 10 V DC; 2 ... 10 V DC; 30 mA max.; resolution:12mV; Ri ? 330 ? (terminal 5+, 6-)
Analog current output0 ... 20 mA; 4 ... 20 mA; resolution: 25 µA; Ri ? 600 ? (terminal 4-, 5+)
Digital incrementing? (Ub -3 V), 20 mA, short-circuit proof (Terminals 1-, 2+)
with frequency division Fin /1 ... Fin /9999

Transfer characteristics

Input frequency? 40000 Hz, pulse pause/pulse length: ? 12µs
Deviation? 0.2 % of full-scale value
Changing interval5 ms (Internal processing time)

Standard conformity

Electromagnetic compatibilityacc. to EN 50081-2 / EN 50082-2

Ambient conditions

Ambient temperature-25 ... 40 °C (-13 ... 104 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humiditymax. 80%, not condensing
Altitude0 ... 2000 m
Operating conditionsThe device has only to be used in an indoor area.

Mechanical specifications

Connection assemblyCaution: Please be aware that the device may only be connected to a switchable power supply. The switch or circuit breaker must be easy to reach and identified as the separator for the device.
Degree of protectionIP20
Connectionremovable terminals , max. core cross section 0.2 mm2 ... 2.5 mm2
Construction typemodular terminal housing in Makrolon, System KF
For use in the switch cabinet/switch cabinet module
Mountingsnap-on to 35 mm standard rail or screw fixing

 

По вопросу интересующей Вас продукции, пожалуйста, свяжитесь с нами:

  

8 (029) 555-8-000

  

8 (044) 555-8-000

 

8 (017) 255-8-000

Был online: Давно
OOO "ФилФар Технолоджи"
Рейтинг не сформирован
10 лет на Deal.by

Frequency voltage current converter KFU8-FSSP-1.D-Y322444

Под заказ
Цену уточняйте
Доставка
Оплата и гарантии