General specifications

Switching function2 x normally open (NO)
Output typeTwo-wire
Rated operating distance2.5 mm
Installationfor non-flush mounting
Output polarityDC
Assured operating distance0 ... 2.05 mm
Output type2x 2-wire

Nominal ratings

Operating voltage6 ... 30 V
Switching frequency0 ... 100 Hz
Hysteresistyp. 0.5 mm
Reverse polarity protectionreverse polarity tolerant
Short-circuit protectionno
Voltage drop? 6 V
Operating current4 ... 100 mA
Off-state current100 ... 200 µA typ. 160 µA

Functional safety related parameters

MTTFd684 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %

Valve circuit

Voltagemax. 32 V DC
Currentmax. 240 mA
Short-circuit protectionno
Reverse polarity protectionyes, with reversed output LED is out of function, therfore more power for solenoid valve

Compliance with standards and directives

Standard conformity

Ambient conditions

Ambient temperature-40 ... 75 °C (-40 ... 167 °F) , restriction for use in hazardous area, see instruction manual
Storage temperature-40 ... 85 °C (-40 ... 185 °F)

Mechanical specifications

Connection (system side)M20 x 1.5 cable gland , ground connection with earthing screw only for wire cross-section 4 mm2, use solid wire or stranded wire with wire end ferrule
Connection (valve side)screw terminal ,
Cable gland M20 x 1.5
Housing materialrugged polycarbonate (PC) + GF 10% , optimised for outdoor use
Housing basepowder coated aluminum
Degree of protectionIP67 ; additional degree of protection IP66/IP69 with BT65-F31K2-RG-EN-01 and SH-F31K2-B13
Terminal assembly
Tightening torque, fastening screws2 Nm
Tightening torque, housing screws1.5 Nm
Tightening torque, earthing screw1.5 Nm
Tightening torque, cable glandmax. 4 Nm
Tightening torque, stopping plug2 Nm

Equipment protection level Gc (nA)

CertificatePF 15CERT3754 X
CE marking[*PD-Z02586A*]
ATEX markingEx-Hexagon II 3G Ex nA IIC T6...T1 Gc
The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-15:2010
Ignition protection category "n"
Use is restricted to the following stated conditions
Special conditions

Equipment protection level Dc (tc)

CE marking[*PD-Z02586A*]
ATEX markingEx-Hexagon II 3D Ex tc IIIC T80°C Dc
The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN